Multizone Office Building

This study provides an open-source dataset of the measured weather data, building indoor data, and system data under the different test settings. The test building is the two-story Flexible Research Platform building at the US Department of Energy’s Oak Ridge National Laboratory, in Oak Ridge, Tennessee. Four heating tests and three cooling tests were conducted. The 1-min interval of weather, building indoor data, and system data from each test setting are provided. Actual weather data were collected from a weather station installed on the roof. This paper describes information on the test building and installed sensors, data collection method, and data validation. The provided dataset can be employed to understand HVAC system conditions and building indoor conditions under different HVAC system operations and the performance of building envelope without HVAC system operation using free-floating test data. Additionally, it can be used for empirical validation of the building energy modelling engine.

Use case:
HVAC Performance Analysis and Building Energy Modeling Validation

Example Observation• Weather: outdoor dry-bulb (°C), relative humidity (%), solar irradiance (W m⁻²), wind speed (m s⁻¹)
• Indoor: 8 zone air temperatures (°C), 8 zone RH (%), CO₂ ppm
• HVAC system states:
– Supply-air temp, return-air temp, mixed-air temp (°C)
– Fan speed (%), damper positions, static pressure (Pa)
– Valve positions for chilled- and hot-water coils (%)
– Equipment statuses (compressor ON/OFF, boiler firing rate, economiser flag)
• Temporal: minute of day, day type (week/week-end)
Example Action1. Supply-air temperature set-point (16 – 18 °C cooling, 28 – 32 °C heating)
2. VAV static pressure set-point (200 – 400 Pa)
3. Global chilled-water valve bias (0–100 %)
4. Global hot-water valve bias (0–100 %)
5. Economiser enable (binary)
Example Reward𝑟ₜ = − (Elec ₜ · cₑ + Gas ₜ · c_g) − λ · Σ_z max(0, |T_zₜ − T_set| − Δ)
• first term: monetary energy cost (€/min)
• second term: comfort penalty (λ ≈ 5 €/K·min, Δ = 0.5 K dead-band)
Large negative spike (−100) if any zone exceeds 27 °C or goes below 18 °C (hard safety).